Free Software Download Center
Software for industrial data collection, monitoring, and analysis.
In order to use the LIVE DASH web reporting component, the LIVE EVENTS software must first be installed and configured according to the required installation and configuration procedures.
Before LIVE DASH is enabled, LIVE EVENTS must be configured so that it can connect to the relevant SCADA and/or Event Recorder systems, access the required data archives, and keep the necessary services active.
The required settings for the LIVE DASH component to access the HTTP publishing service through LIVE EVENTS must be configured in the EOSliveevents.xml configuration file.
<HTTPYayinAktif>True</HTTPYayinAktif>
<YayinServerIP>192.168.1.50</YayinServerIP>
<HTTPYayinPortu>80</HTTPYayinPortu>
LIVE EVENTS automatically prepares the report data used by LIVE DASH in the background. The <DTStartLimit> parameter in EOSliveevents.xml is used to define the date from which this preparation process should begin.
The <DTStartLimit> value specifies the starting date from which LIVE EVENTS begins preparing data for LIVE DASH reports. From this date onward, the data required for reports is automatically preprocessed and archived.
<DTStartLimit>01.01.2025</DTStartLimit>
In this example, LIVE EVENTS will begin preparing data for LIVE DASH reports starting from 01.01.2025.
Preparing the data in advance in the background allows reports to be delivered more quickly when requested, without requiring the relevant data to be recalculated at the time of the report request.
The LIVE DASH component supports the live data feature. This feature allows the latest state of the relevant data to be displayed live in report blocks where individual data is requested.
The live data update frequency is defined by the <LiveDataRefresh> parameter in the EOSliveevents.xml file. The value is specified in milliseconds (ms).
<LiveDataRefresh>5000</LiveDataRefresh>
After completing the configuration changes, the EOSliveevents.xml configuration file must be saved.
For the settings to take effect, the EOSLiveEvents.exe application or the relevant LIVE EVENTS services must be restarted.
After the configuration has been completed and EOSLiveEvents.exe has been restarted, an HTTP LED indicator showing the HTTP publishing status appears on the status bar at the bottom of the LIVE EVENTS application.
After the required checks and corrections have been completed, LIVE EVENTS should be restarted and the HTTP LED status should be verified again.
If the HTTP publishing service is running, the LIVE DASH web interface can be accessed through any Internet browser.
Enter the following address in the browser's address bar using the <YayinServerIP> and <HTTPYayinPortu> values:
http://<YayinServerIP>:<HTTPYayinPortu>
Example:
http://192.168.1.50:8080
If the <HTTPYayinPortu> value is 80, it is not necessary to specify the port number separately.
http://192.168.1.50
After accessing the LIVE DASH web interface, the user is presented with the LOGIN page.
On this screen, users can log in to the LIVE DASH system using any valid username and password defined in the SCADA project.
LIVE DASH uses the existing user and authorization infrastructure of the SCADA system for user authentication. This provides controlled access using existing SCADA users without requiring separate user definitions.
After the username and password have been entered correctly, the LIVE DASH Home Page is displayed. Successfully opening the home page indicates that the LIVE EVENTS and LIVE DASH components have been configured correctly and that the installation has been successfully completed.
After the installation is complete, the reports to be displayed in the LIVE DASH web interface must be created. For this purpose, the ReportDesigner.exe application located in the LIVE EVENTS program directory is used to design the required reports through the Web Reporting Tool.
Report design includes steps such as selecting report blocks, defining data sources, specifying time ranges, and configuring visual components. Detailed information about these stages is covered in the relevant report design documentation.
| Step | Operation |
|---|---|
| 1 |
Verify that the LIVE EVENTS software has been properly configured.
|
| 2 | Define the HTTP publishing settings in EOSliveevents.xml. |
| 3 | Define the starting date for LIVE DASH report data preparation using DTStartLimit. |
| 4 | Define the live data update interval using LiveDataRefresh. |
| 5 | Save EOSliveevents.xml and restart LIVE EVENTS. |
| 6 | Verify the status of the HTTP publishing service by checking the HTTP LED indicator. |
| 7 | Access the LIVE DASH web interface through a browser. |
| 8 | Log in using valid user credentials defined in the SCADA system. |
| 9 | Display the LIVE DASH Home Page and then proceed to report design using ReportDesigner. |